Shaanxi Shinhom Enterprise Co.,Ltd

Shaanxi Shinhom Enterprise Co.,Ltd A Worldwide Leading Supplier Of Magnetic Components

Manufacturer from China
Verified Supplier
7 Years
Home / Products / Split Core Current Transformer /

600A Permalloy Split Core Current Transformer 1.0 Class

Contact Now
Shaanxi Shinhom Enterprise Co.,Ltd
Visit Website
Province/State:Shaanxi
Country/Region:china
Contact Person:MrJack wang
Contact Now

600A Permalloy Split Core Current Transformer 1.0 Class

Ask Latest Price
Video Channel
Brand Name :Shinhom
Model Number :ACST Series
Certification :RoHS
Place of Origin :China
MOQ :Negotiation
Price :Negotiation
Payment Terms :T/T
Supply Ability :10000/MONTH
Delivery Time :4~8 Weeks
Packaging Details :Carton
Current range :5~600A
Output :0-500mA or 0.333VAC
Class :0.5、1.0
Case :Plastic
Customizable :Yes
Coil :Permalloy Core
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Low voltage 5A~600A Input 333mV 500mV Output Split Coil Current Transformer,High Accuracy
Split core current transformer are designed for fast and easy installation.The split core design permits non-contact current measurements through magnetic field induction without requiring that the primary wire be taken offline and disconnected for CT installation.This method permits a safer,easier and portable current measurement. An internal precision burden resistor across the secondary winding of the CT provides a safe low voltage output and permits safe opening of the secondary

Features:

  • The structure of the self-locking, safe, easy to install, portable
  • Wide inner window, allowing clamping of big cables or bus-bars
  • Wide range of sizes to accommodate all the existing installations
  • Isolated plastic case recognized according to UL94-V0
  • Wires plugs, Audio plugs, Power plugs and so on five kinds of plugs


Applications:

  • Current measurement, monitoring and protection for electrical wiring and equipment.
  • Current and power measurement for electric motors, lighting, air compressor, heating and ventilation system, air-condition equipment and automation – control system.
  • Current, power and energy monitoring device.
  • Relay protection device.


Mechanical Parameter

Electrical ParameterMechanical Parameter
Frequency50-2KHzCasePA/UL94-V0
Rated Input5A-200ABobbinPBT
Measuring range10%In-120%InCoreSilicon steel
Rated Output0.333V(AC)or 0-500mAInternal structureEpoxy
Ratio≤ ± 1.0%ConstructionTie
Phase angle≤ ±60minOperation Temp-25oC~+75oC
Dielectric strangth2.5KV/1mA/1minOperating Humidity≤85%
Insulation ResistanceDC500V/100MΩ minOutput ConnectionUL1015 20AWG Wire2.5m

MODELACST
Current Ratio300A/100mA400A/40mA500A/50mA600A/60mA300~600A/0.333V
Primary Current300A400A500A600A300~600A
Max.Current360A480A600A720A720A
Output100mA40mA50mA60mA333mV
Load Resistance50Ω/
Class0.5/1.0
Turns Ratio3000:110000:110000:110000:1/
Protection Level7.5V0-P7.5V0-P7.5V0-P7.5V0-P7.5V0-P
Insulation CategoryCATIII
Operating Condition-20℃~+50℃,≤85%RH,No condensation,IN-house&Any direction installable
Storage Condition-30℃~+50℃,≤85%RH,No condensation

Note: The Current Ratio above are common type, that's ok to customise the ration according to

customers' requirement.


Notes: Product specifications can be customized







Inquiry Cart 0